This practical guide shows you how to complete a signed, QR-verified UPS Battery Thermal Runaway & BMS Audit certificate in OhmCert Module #20 and how to troubleshoot non-compliant readings on site.

1. Step-by-Step OhmCert UI Workflow

  1. Open Module #20: Navigate to UPS Battery Thermal Runaway & BMS Audit from the Dashboard.
  2. Load a 1-Click Standard Annex Preset: Open the blue Standard Annex banner at the top and click a preset (such as "Healthy VRLA Cabinet (Tcell=25.5C, Tamb=23.0C, Spread=1.2C)") to populate target limits automatically.
  3. Enter Your Field Measurements: Fill in the measured inputs (Maximum Cell Temperature, Room Ambient Temperature, Cell-to-Cell Temperature Spread, Float Voltage Deviation, Highest Cell Internal Resistance, Baseline Internal Resistance, Float Charge Current, Baseline Float Charge Current). Blank inputs stay neutral PENDING.
  4. Complete the 17-Point Checklist: Grade each item, attach photos if needed, and export the SHA-256 signed PDF certificate.

2. Worked Numerical Field Case Study

Scenario: Healthy VRLA Cabinet (Tcell=25.5C, Tamb=23.0C, Spread=1.2C) (NFPA 855 / IEEE 1188) — Normal temperature-compensated float operation..

  • Maximum Cell Temperature: 25.5 degC
  • Room Ambient Temperature: 23.0 degC
  • Cell-to-Cell Temperature Spread: 1.2 degC
  • Float Voltage Deviation: 0.4 %
  • Highest Cell Internal Resistance: 4.2 mOhm
  • Baseline Internal Resistance: 3.9 mOhm
  • Float Charge Current: 0.18 A
  • Baseline Float Charge Current: 0.15 A

3. Engineering Troubleshooting: Corrective Actions When a Reading Fails

  1. Immediately isolate any battery string exhibiting simultaneous Delta-T > 5 degC over ambient and float current > 1.5x baseline.
  2. Replace individual monoblocks whose internal ohmic resistance has risen > 50% above baseline (shorted/drying cells).
  3. Verify temperature-compensation probe placement on the negative pilot cell and calibrate H2 gas extraction fan boost interlocks.

→ Try This Worked Example Live in Module #20 (Battery Thermal / BMS Audit)