#20UPS Battery Thermal Runaway & BMS Audit

Project Framework (report reference): IEC 60364-4-41Applicable Standard: NFPA 855 / IEEE 1188

Multi-Asset / Multi-Point Equipment Schedule

Inspect multiple transformers, panels, rooms, motors, or RCDs in this module without overwriting previous assets. Each item receives a permanent QR Sticker UID preserved across annual audits.

Sticker UID: OC-BATT-CD48

Standard Limits, Equations & Space Presets

NFPA 855 & IEEE 1188 Stationary Energy Storage thermal runaway diagnostics: cell-to-ambient temperature rise, float current runaway escalation, and cell ohmic trend.

One-Click Normative Presets (Auto-fills Target Limits)

Measured Inputs

Calculated / Evaluated Results

Thermal runaway screening combines cell-to-ambient delta T, float current trend and ohmic rise against baseline. Numeric triggers follow IEEE 1188 trending guidance and OEM data; NFPA 855 governs spacing, detection and suppression in the checklist.

Pending / Not tested — results stay neutral until valid measured values are entered.

  • Cell Delta T vs Ambient

    - degC

    Not tested - enter the measured value. Acceptance: Delta T <= 5 degC; rising cell temperature together with rising float current is the classic runaway signature [IEEE 1188 §6 / OEM guidance]

    Pending
  • Cell-to-Cell Temperature Spread

    - degC

    Not tested - enter the measured value. Acceptance: Spread <= 3 degC across the string [Field convention]

    Pending
  • Float Voltage Deviation

    - %

    Not tested - enter the measured value. Acceptance: Within +/-2% of the temperature compensated float set point [IEEE 1188 §6.2]

    Pending
  • Internal Resistance Rise vs Baseline

    - %

    Not tested - <= 20% rise: acceptable. [IEEE 1188 §6.4]

    Pending
  • Float Current Rise vs Baseline

    - %

    Not tested - enter the measured value. Acceptance: A float current sustained more than about 50% above baseline at constant temperature indicates runaway onset [IEEE 1188 Annex / OEM guidance]

    Pending

Verification Checklist (0 / 17)

Pending
  • 1Battery Management System (BMS / cell-monitoring system) online with 100% of strings, blocks, and individual cell sensors reporting

  • 2Cell negative-post temperature sensors cross-calibrated against calibrated infrared thermal camera (Delta T <= 5 degC over ambient) [IEEE 1188]

  • 3Cell-to-cell temperature spread across each string verified <= 3.0 degC with no localised air-conditioning dead zones

  • 4Temperature-compensated float charging (-3 mV/cell/degC for VRLA) enabled and verified functional on UPS rectifier

  • 5Steady-state float charge current trend reviewed (> 50% rise at constant voltage/temp flags exothermic thermal runaway onset)

  • 6Individual cell float voltages verified within +/-2% of nominal and <= 0.05 V string spread

  • 7Internal ohmic resistance / conductance measured on every block; cells > +20% above baseline flagged, > +50% scheduled for immediate replacement [IEEE 1188 §6.4]

  • 8Infrared thermography scan of all inter-cell busbars, tier cables, and DC breaker terminals completed under current flow

  • 9VRLA pressure relief valves inspected for dry salt encrustation, electrolyte weeping, or container pillowing/swelling

  • 10Li-ion BESS rack-level / module-level BMS over-voltage, under-voltage, over-current, and over-temperature contactor trip interlocks proven [UL 1973 / UL 9540A]

  • 11Battery room HVAC redundancy (N+1 cooling) and dedicated hydrogen / off-gas extraction airflow rate verified [EN 50272-2 / NFPA 855]

  • 12Hydrogen (H2) and thermal runaway off-gas (CO / VOC) gas detectors calibrated and interlocked to boost extraction fan at 1% LEL (25% of 4% LEL) and trip DC breaker at 2% LEL

  • 13Very Early Warning Aspirating Smoke Detection (VESDA) and clean-agent / water-mist fire suppression operational in battery room [NFPA 855 §4.9]

  • 14Minimum separation clearances between battery racks and fire-rated enclosure barriers maintained per NFPA 855

  • 15Remote DC battery disconnect / shunt-trip pushbutton accessible outside battery room entrance door and clearly labelled

  • 16BMS high-temperature, high-float-current, and impedance-drift critical alarms verified end-to-end with 24/7 NOC / BMS

  • 17Defective cell replacement log, torque records, and hazardous waste disposal manifests updated