#15Lightning Protection System (LPS) & SPD Engineering Audit
Multi-Asset / Multi-Point Equipment Schedule
Inspect multiple transformers, panels, rooms, motors, or RCDs in this module without overwriting previous assets. Each item receives a permanent QR Sticker UID preserved across annual audits.
Sticker UID: OC-LPS0-75C8Standard Limits, Equations & Space Presets
Comprehensive IEC 62305-1/2/3/4 Lightning Protection engineering engine: collection area Ad, annual strike risk ND, rolling sphere & mast protection radius rp, down-conductor count, separation distance s = ki·kc·l/km, minimum electrode length l1, and SPD effective protection level Up/f.
Ad = L·W + 6H(L+W) + 9·pi·H^2 | ND = Ng x Ad x 10^-6
Equivalent collection area (m2) of isolated structure and expected direct lightning flashes per year (IEC 62305-2 Annex A).
rp = sqrt(h x (2r - h))
Protected radius on horizontal plane for air-termination mast height h and rolling sphere radius r (IEC 62305-3 §5.2.2).
s = (ki x kc / km) x l
Minimum separation distance (m) to prevent dangerous sparking between LPS and internal metallic installations (IEC 62305-3 §6.3).
IEC 62305-3 Table 2 & Table 4: LPS Class Geometry & Separation Coefficients
IEC 62305-3 §5.2 & §6.3| LPS Class (LPL) | Peak Current I_max / I_min | Rolling Sphere Radius r | Max Mesh Size | Down-Conductor Spacing | Coefficient ki |
|---|---|---|---|---|---|
| Class I (LPL I) | 200 kA / 3 kA | r = 20 m | 5 x 5 m | 10 m | ki = 0.08 |
| Class II (LPL II) | 150 kA / 5 kA | r = 30 m | 10 x 10 m | 10 m | ki = 0.06 |
| Class III (LPL III) | 100 kA / 10 kA | r = 45 m | 15 x 15 m | 15 m | ki = 0.04 |
| Class IV (LPL IV) | 100 kA / 16 kA | r = 60 m | 20 x 20 m | 20 m | ki = 0.04 |
Material factor km: Air = 1.0, Concrete / Brick / Wood = 0.5. Partitioning factor kc: 1 conductor = 1.0, 2 conductors = 0.66, 3+ conductors / mesh / ring earth = 0.44.
Measured Inputs
IEC 62305 Collection Area, Rolling Sphere, Separation Distance & SPD Evaluation
Parametric IEC 62305-2/3/4 calculator: evaluates structure Equivalent Collection Area Ad & annual direct strike frequency ND, Rolling Sphere & Air-Termination Mast protection cone radius rp, perimeter down-conductor count, Separation Distance s = (ki x kc / km) x l, minimum earth electrode length l1 from soil resistivity rho, and SPD effective protection level Up/f.
Pending / Not tested — results stay neutral until valid measured values are entered.
- Pending
Protection Level Class II Normative Geometry
Rolling sphere r = 30 m | Mesh 10 x 10 m | Max down spacing 10 m
IEC 62305-3 Table 2 & Table 4 geometric criteria for the selected Lightning Protection Level (LPL).
- Pending
Collection Area Ad & Annual Strike Frequency ND (IEC 62305-2)
-
Calculated per IEC 62305-2 Annex A.2 (Ad = L·W + 6H(L+W) + 9·pi·H^2) at Ng = 2.5 flashes/km2/yr.
- Pending
Air-Termination Mast Protected Cone Radius rp (IEC 62305-3 §5.2.2)
-
Rolling sphere protected radius rp = sqrt(h x (2r - h)) around air-termination rod.
- Pending
Perimeter Down-Conductor Count Adequacy
-
Not tested - enter the measured value. Acceptance: At least 2 down conductors and <= 10 m average spacing around perimeter for Class II [IEC 62305-3 §5.3.3 & Table 4]
- Pending
Separation Distance s = (ki x kc / km) x l
-
Not tested - enter the measured value. Acceptance: Actual separation s_actual >= calculated s to prevent side-flashing, otherwise bond directly [IEC 62305-3 §6.3 / Table 4]
- Pending
Earth Termination Resistance & Min Electrode Length l1
- Ohm
Not tested - enter the measured value. Acceptance: RA <= 10 Ohm combined earth termination (measured isolated from protective earth) and electrode length >= l1 [IEC 62305-3 §5.4.1 & Figure 2]
- Pending
Down Conductor & Test Joint Continuity
- Ohm
Not tested - enter the measured value. Acceptance: End-to-end metallic continuity from air-termination through test joint to earth <= 0.20 Ohm [IEC 62305-3 Annex E.5]
- Pending
SPD Effective Protection Level Up/f = Up + Delta_U(lead)
-
Not tested - enter the measured value. Acceptance: Effective protection voltage Up/f <= 2.5 kV (Category II Uw) and total SPD lead length <= 0.50 m [IEC 62305-4 / IEC 60364-5-53 §534.4.4 & §534.4.8]
Verification Checklist (0 / 20)
1Lightning Risk Assessment (R1, R2, R3, R4 vs tolerable risk RT = 10^-5) documented per IEC 62305-2
2Air-termination system (rods, catenary wires, or meshed conductor grid) covers all roof corners and parapets [IEC 62305-3 §5.2]
3Rooftop HVAC units, chillers, PV frames, vents and antennas positioned inside Rolling Sphere / lp cone or protected by isolated air terminals
4Conductor cross-sections comply with IEC 62305-3 Table 6 ( >= 50 mm2 Cu/Al or >= 50 mm2 hot-dip galvanized steel, min 8 mm dia rod)
5Down conductors routed straight and vertically with no sharp bends (radius R >= 20 cm) or re-entrant loops
6Down-conductor perimeter spacing complies with LPL Class (10 m Class I/II, 15 m Class III, 20 m Class IV) [IEC 62305-3 Table 4]
7Disconnecting test joint fitted on every down conductor at 1.5 - 2.0 m above ground and labelled
8Calculated separation distance s maintained between LPS and internal metal pipes/cable trays, or equipotential bonding installed
9Type A (vertical/radial rods >= l1) or Type B (ring conductor >= 80% in soil contact at >= 0.5 m depth) earth termination verified
10Foundation earth electrode (Ufer ground) interconnected to main earthing busbar via stainless steel (V4A / AISI 316) exit risers
11Earth inspection pits accessible, drained, labelled, and clamp connections coated with anti-corrosion petrolatum tape
12Bimetallic connectors (Cu-Al / Cu-Fe) installed at all dissimilar metal transitions to prevent galvanic corrosion
13Lightning Equipotential Bonding (LEB) at LPZ 0A/1 boundary verified for water, gas, fire sprinkler, and structural steel
14Type 1 (10/350 us impulse, Iimp >= 12.5 kA/pole) SPD installed at main LV switchboard incomer
15Coordinated Type 2 (8/20 us) SPDs fitted at sub-distribution boards where cable distance from Type 1 exceeds 10 m
16SPD connecting leads (Line + PE / V-wiring) kept straight and <= 0.50 m total length [IEC 60364-5-53 §534.4.8]
17SPD status indicators healthy (green), remote alarm dry contact wired, and dedicated backup fuse/MCB coordinated
18Data, telecom, coax and rooftop PV DC strings protected with Type 1/2 surge arresters at building entry
194-wire micro-ohmmeter continuity (<= 0.2 Ohm) and isolated earth resistance measurements logged per down conductor
20As-built LPS layout drawing, rolling sphere diagram, and periodic inspection schedule (1-2 yr Class I/II, 2-4 yr Class III/IV) signed off