One of the most frequent questions engineers ask before inspecting MV/HV Protection Relay Setting Calculator is: "Which standard should I cite on the certificate, and where do the pass/fail limits come from?" This reference guide maps IEC 60255 / IEEE C37 to national regulatory adoptions and provides the complete standard annex tables.

1. National & Regional Standard Equivalence Matrix

Region / LanguageAdopted National Standard & Regulatory Code
International / UK (EN)IEC 60255 / IEEE C37
Turkey (TR · Türkçe)TS EN 60255-151 / IEEE C37.112 / TEİAŞ
Germany / DACH (DE · Deutsch)DIN EN 60255-151 / VDE-AR-N 4110
France (FR · Français)NF EN 60255-151 / NF C 13-100
Spain (ES · Español)UNE-EN 60255-151 / IEEE C37.112
Italy (IT · Italiano)CEI EN 60255-151 / CEI 0-16
Gulf / Middle East (AR · العربية)IEC 60255 / IEEE C37 / SASO / DEWA / ADDC

2. Normative Acceptance Criteria & Mathematical Basis

IEC 60255-151 & IEEE C37.112 characteristic: t = ((k / (M^a - 1)) + c) x TMS with M = If / Is. Grading against the downstream device uses the 0.30 s discrimination margin. Requires explicit TMS input (never assumed).

t_IEC: t = TMS x [ k / ((If / Is)^alpha - 1) ] — IEC 60255-151 inverse-time operating equation for fault multiple M = If / Is > 1.0.

t_IEEE: t = (TD / 7) x [ A / (M^p - 1) + B ] — IEEE C37.112 operating equation where TD/7 maps to TMS = 0..1.0.

Delta_t: Delta_t = t_upstream - t_downstream >= 0.25 s (0.30 s target) — Coordination Time Interval (CTI) accounting for CB opening time (50-80 ms), relay overshoot, and CT errors.

3. Official Standard Reference Tables

IEC 60255-151 & IEEE C37.112 Overcurrent Relay Curve Constants (IEC 60255-151 Table 1 / IEEE C37.112 Table 1)

Curve DesignationStandardConstant k (or A)Exponent alpha (or p)Constant BTypical Engineering Application
IEC Standard Inverse (SI)IEC 60255-1510.140.020General radial distribution feeders & industrial incomers
IEC Very Inverse (VI)IEC 60255-15113.51.000Long lines where fault current drops rapidly with distance
IEC Extremely Inverse (EI)IEC 60255-15180.02.000Grading with HRC fuses, transformer thermal withstand & motor reacceleration
IEC Long Time Inverse (LTI)IEC 60255-151120.01.000Standby earth fault (SBEF) & neutral displacement protection
IEEE Moderately Inverse (MI)IEEE C37.1120.05150.020.1140North American industrial feeders & tie breakers
IEEE Very Inverse (VI)IEEE C37.11219.612.000.4910Substation feeders with variable source impedance
IEEE Extremely Inverse (EI)IEEE C37.11228.202.000.1217Distribution transformers & fuse-saving schemes

→ Launch Module #04 with Interactive Standard Annex Tables