This practical guide shows you how to complete a signed, QR-verified MV Switchgear, VCB/SF6 Breaker & MV Cable VLF Test Report certificate in OhmCert Module #30 and how to troubleshoot non-compliant readings on site.
1. Step-by-Step OhmCert UI Workflow
- Open Module #30: Navigate to MV Switchgear, VCB/SF6 Breaker & MV Cable VLF Test Report from the Dashboard.
- Load a 1-Click Standard Annex Preset: Open the blue Standard Annex banner at the top and click a preset (such as "34.5 / 36 kV Primary Substation Vacuum Circuit Breaker (VCB) + XLPE Feeder") to populate target limits automatically.
- Enter Your Field Measurements: Fill in the measured inputs (Rated Medium Voltage System Level Ur, Circuit Breaker Interruption Medium, OEM Max Main Contact Resistance Limit, Measured Contact Resistance Pole L1 (at >= 100 A DC), Measured Contact Resistance Pole L2 (at >= 100 A DC), Measured Contact Resistance Pole L3 (at >= 100 A DC), Measured Breaker Opening Time Pole L1, Measured Breaker Opening Time Pole L2, Measured Breaker Opening Time Pole L3, Worst-Case Breaker Closing Time (Max Pole), Main Pole Insulation Resistance (at 5 kV DC), MV XLPE Cable 0.1 Hz VLF Tan-Delta at Uo (10^-3, optional)). Blank inputs stay neutral
PENDING. - Complete the 12-Point Checklist: Grade each item, attach photos if needed, and export the SHA-256 signed PDF certificate.
2. Worked Numerical Field Case Study
Scenario: 34.5 / 36 kV Primary Substation Vacuum Circuit Breaker (VCB) + XLPE Feeder (IEC 62271-100 36 kV) — Healthy 1250 A withdrawable VCB cubicle and 34.5 kV XLPE feeder VLF tan-delta check..
- Rated Medium Voltage System Level Ur:
36.0 kV - Circuit Breaker Interruption Medium:
Vacuum Circuit Breaker (VCB) - OEM Max Main Contact Resistance Limit:
60 uOhm - Measured Contact Resistance Pole L1 (at >= 100 A DC):
34 uOhm - Measured Contact Resistance Pole L2 (at >= 100 A DC):
36 uOhm - Measured Contact Resistance Pole L3 (at >= 100 A DC):
35 uOhm - Measured Breaker Opening Time Pole L1:
38.2 ms - Measured Breaker Opening Time Pole L2:
38.8 ms - Measured Breaker Opening Time Pole L3:
38.5 ms - Worst-Case Breaker Closing Time (Max Pole):
54.0 ms - Main Pole Insulation Resistance (at 5 kV DC):
12500 MOhm - MV XLPE Cable 0.1 Hz VLF Tan-Delta at Uo (10^-3, optional):
1.2 E-3
3. Engineering Troubleshooting: Corrective Actions When a Reading Fails
- Inspect, clean, or replace withdrawable tulip finger contacts or vacuum interrupters if contact resistance exceeds OEM uOhm limits or 50% inter-pole deviation.
- Lubricate hardened operating mechanism latches or replace sluggish trip coils when opening time or > 2.0 ms pole discrepancy fails.
- Localize damp cable joints or degraded terminations via VLF partial-discharge mapping if 0.1 Hz tan-delta exceeds 4.0 x 10^-3.
→ Try This Worked Example Live in Module #30 (MV Switchgear & VCB/VLF)