This practical guide shows you how to complete a signed, QR-verified Ex-Proof / ATEX & IECEx Hazardous Area Electrical Inspection certificate in OhmCert Module #26 and how to troubleshoot non-compliant readings on site.
1. Step-by-Step OhmCert UI Workflow
- Open Module #26: Navigate to Ex-Proof / ATEX & IECEx Hazardous Area Electrical Inspection from the Dashboard.
- Load a 1-Click Standard Annex Preset: Open the blue Standard Annex banner at the top and click a preset (such as "Zone 1 Hydrogen / Refinery Area (Ex d IIC T4 Gb Motor/Junction, AIT=500C)") to populate target limits automatically.
- Enter Your Field Measurements: Fill in the measured inputs (Classified Hazardous Area Zone (IEC 60079-10), Installed Equipment Protection Level (EPL), Site Required Gas / Dust Group, Equipment Marked Gas / Dust Group, Equipment Temperature Class (Group II), Gas / Vapour / Dust Cloud Auto-Ignition Temp (AIT), Ex Enclosure to Equipotential Bonding Continuity, Ex e Motor Overload Relay Trip Time vs tE (at IA/IN), Ex i Barrier Max Output Voltage Uo (optional), Ex i Field Device Max Input Voltage Ui (optional), Ex i Barrier Max External Capacitance Co (optional), Ex i Total Cable + Instrument Capacitance Ci+Cc (optional)). Blank inputs stay neutral
PENDING. - Complete the 22-Point Checklist: Grade each item, attach photos if needed, and export the SHA-256 signed PDF certificate.
2. Worked Numerical Field Case Study
Scenario: Zone 1 Hydrogen / Refinery Area (Ex d IIC T4 Gb Motor/Junction, AIT=500C) (IEC 60079 Zone 1 IIC) — Flameproof Ex d IIC T4 Gb equipment in Zone 1 Hydrogen (IIC) environment..
- Classified Hazardous Area Zone (IEC 60079-10):
Zone 1 (Gas - Likely in normal operation) - Installed Equipment Protection Level (EPL):
Gb (Ex d / Ex e / Ex ib / Ex px) - Site Required Gas / Dust Group:
IIC (Hydrogen / Acetylene / Carbon Disulphide) - Equipment Marked Gas / Dust Group:
IIC (covers IIC, IIB, IIA) - Equipment Temperature Class (Group II):
T4 (<= 135 degC) - Gas / Vapour / Dust Cloud Auto-Ignition Temp (AIT):
500 degC - Ex Enclosure to Equipotential Bonding Continuity:
0.08 Ohm - Ex e Motor Overload Relay Trip Time vs tE (at IA/IN):
8 s - Ex i Barrier Max Output Voltage Uo (optional):
28 V - Ex i Field Device Max Input Voltage Ui (optional):
30 V - Ex i Barrier Max External Capacitance Co (optional):
83 nF - Ex i Total Cable + Instrument Capacitance Ci+Cc (optional):
45 nF
3. Engineering Troubleshooting: Corrective Actions When a Reading Fails
- Immediately de-energize and replace any apparatus whose EPL, Gas/Dust Group, or Temperature Class violates the Zone hierarchy.
- Replace non-compliant cable glands with certified Ex d barrier glands or Ex e glands fitted with manufacturer shroud/locking washers and thread seal.
- Shorten Ex i field cable runs or select low-capacitance instrumentation cable (< 80 pF/m) where C_c + C_i exceeds barrier C_o.
→ Try This Worked Example Live in Module #26 (Ex-Proof / ATEX (IEC 60079))