#27RCD / Residual Current Device Trip Time & Ramp Test Report
Multi-Asset / Multi-Point Equipment Schedule
Inspect multiple transformers, panels, rooms, motors, or RCDs in this module without overwriting previous assets. Each item receives a permanent QR Sticker UID preserved across annual audits.
Sticker UID: OC-RCD0-A3A3Standard Limits, Equations & Space Presets
IEC 60364-6 §6.4.3.7, EN 61008-1 (RCCB), and EN 61009-1 (RCBO) verify residual current devices across 0.5x non-trip hold, 1x IΔn (0° & 180°), 5x IΔn fast disconnection (<= 40 ms for 30 mA additional protection), sinusoidal ramp trip threshold (0.5-1.0 x IΔn), and contact voltage Uc <= 50 V.
Measured Inputs
Calculated / Evaluated Results
Evaluates Residual Current Devices (RCCB / RCBO / CBR) across 0.5x non-trip hold, 1x IΔn (0 deg / 180 deg), 5x IΔn fast disconnection, sinusoidal ramp threshold I_Δtrip, and contact voltage Uc per IEC 60364-6 §6.4.3.7, EN 61008-1 Table 1, and BS 7671 Regulation 643.8.
Pending / Not tested — results stay neutral until valid measured values are entered.
- Pending
0.5x IΔn Non-Operating Hold Verification
-
Not tested - enter the measured value. Acceptance: RCD must NOT trip at 0.5x IΔn test current [EN 61008-1 Table 1 / IEC 60364-6]
- Pending
Worst-Case Break Time at 1x IΔn (max of 0 deg / 180 deg)
- ms
Not tested - enter the measured value. Acceptance: t_trip <= 300 ms for General Non-Delayed RCD at 1x IΔn [EN 61008-1 Table 1 / EN 61009-1]
- Pending
Fast Disconnection Time at 5x IΔn (Additional Protection)
- ms
Not tested - enter the measured value. Acceptance: t_trip <= 40 ms at 5x IΔn (mandatory for IΔn <= 30 mA additional protection) [IEC 60364-4-41 §415.1 / EN 61008-1 Table 1]
- Pending
Sinusoidal Ramp Trip Threshold I_Δtrip
-
Not tested - enter the measured value. Acceptance: 0.50 x IΔn < I_Δtrip <= 1.00 x IΔn under sinusoidal AC ramp [EN 61008-1 §5.3.3]
- Pending
Fault Contact Voltage Uc at Rated IΔn
- V
Not tested - enter the measured value. Acceptance: Uc <= 50 V AC touch voltage safety limit [IEC 60364-4-41 §411.5.3]
Verification Checklist (0 / 12)
1RCD type (Type A / F / B) matches connected load harmonic & DC fault profile (no Type AC on VFD, EVSE, UPS or inverter loads!) [IEC 60364-5-53 §531.3.3]
2Upstream Selective Type S RCD (>= 3x downstream IΔn and time-delayed) coordinated with downstream 30 mA RCDs for total vertical selectivity
3Integral mechanical 'T' (Test) button actuated and verified to trip the breaker cleanly (user quarterly/6-monthly notice affixed)
4RCD tested with downstream loads disconnected (or standing earth leakage current verified < 0.3 x IΔn to avoid false ramp readings)
50.5x IΔn non-trip hold verified at both 0 deg and 180 deg half-cycles without nuisance tripping
61x IΔn disconnection time verified at both 0 deg and 180 deg phase angles (worst-case value recorded)
75x IΔn fast disconnection time (<= 40 ms) verified for all <= 30 mA socket-outlet and personal-protection RCDs [IEC 60364-4-41 §415.1]
8Pulsating DC (0 deg / 180 deg) test verified on Type A / F RCDs and smooth DC (<= 2x IΔn or 6 mA RDC-DD) verified on Type B RCDs
9Neutral (N) and Protective Earth (PE) strictly isolated downstream of every RCD (zero N-PE bridges causing parallel return paths)
10Multi-pole RCD neutral pole verified as early-make / late-break (closes before and opens after phase contacts)
11Short-circuit backup protection (gG fuse / upstream MCCB Inc / IΔc coordination) verified against prospective fault current Ipf
12Enclosure IP rating, DIN-rail clip locking, terminal torque, and circuit directory labeling verified
General Notes