#29AC Induction Motor & VFD Field Diagnostic Report
Multi-Asset / Multi-Point Equipment Schedule
Inspect multiple transformers, panels, rooms, motors, or RCDs in this module without overwriting previous assets. Each item receives a permanent QR Sticker UID preserved across annual audits.
Sticker UID: OC-MOTO-AED5Standard Limits, Equations & Space Presets
NEMA MG-1 §14.36, IEC 60034-1, IEEE Std 43, and IEC 60034-25 define field acceptance limits for 3-phase induction motors and VFD drives: even 3.5% phase voltage unbalance increases winding temperature rise by ~25% (2 x %V_unb^2).
Measured Inputs
Calculated / Evaluated Results
Evaluates 3-phase industrial motors and Variable Frequency Drives (VFD): terminal voltage unbalance & exact NEMA MG-1 §14.36 thermal derating factor (extra rotor/stator heating ~ 2 x %V_unb^2), phase current unbalance, 3-phase winding DC ohmic resistance balance (<= 2%), IEEE 43 stator insulation R_40C, bearing temperature, and IEC 60034-25 VFD shaft EDM voltage.
Pending / Not tested — results stay neutral until valid measured values are entered.
- Pending
Terminal Phase Voltage Unbalance & NEMA MG-1 Derating
-
Not tested - enter the measured value. Acceptance: V_unb <= 1.0% without derating (<= 2.0% max field limit with NEMA MG-1 derating; > 5.0% prohibited) [NEMA MG-1 §14.36 / IEC 60034-1 §7.2]
- Pending
3-Phase Current Unbalance
- %
Not tested - enter the measured value. Acceptance: Phase current unbalance <= 10.0% at normal operating load [ANSI/NETA MTS §7.15.1]
- Pending
Operating Load Factor vs NEMA Derated Capacity
-
Not tested - enter the measured value. Acceptance: I_avg / I_FLC <= 100% x NEMA Derating Factor [IEC 60034-1 / NEMA MG-1]
- Pending
3-Phase Stator Winding DC Resistance Unbalance
-
Not tested - enter the measured value. Acceptance: Max deviation from average phase resistance <= 2.0% (detects shorted turns or loose terminal lugs) [IEEE Std 112 / ANSI/NETA MTS §7.15.1]
- Pending
Stator Winding Insulation Resistance R_40C
- MOhm
Not tested - enter the measured value. Acceptance: R_40C >= 5 MOhm minimum for LV (< 1 kV) stators (>= 100 MOhm recommended for critical drives) [IEEE Std 43-2013 Table 2]
- Pending
Bearing Housing Operating Temperature (DE / NDE)
- degC
Not tested - enter the measured value. Acceptance: Bearing housing temperature <= 80 degC continuous grease-lubricated limit [IEEE 841 / ISO 10816]
- Pending
VFD Shaft-to-Frame EDM Peak Voltage
- Vpk
Not tested - enter the measured value. Acceptance: V_shaft <= 5.0 Vpk to prevent capacitive EDM fluting of motor bearings (install AEGIS shaft grounding ring / insulated NDE bearing if exceeded) [IEC 60034-25 / NEMA MG-1 Part 31]
Verification Checklist (0 / 12)
1Motor nameplate data (kW, V, Hz, I_FLC, cos phi, RPM, IE efficiency class, Insulation Class F/H, IP rating) verified against duty
2Motor efficiency class meets IEC 60034-30-1 regulatory minimum (IE3 / IE4) and cooling fan cowl / stator fins unobstructed
3Terminal box gasket intact, brass/EMC cable glands tight, and star/delta link bars torqued evenly without overheating
4Protective earth (PE) terminal inside motor box and external frame supplementary earth lug bonded (< 0.1 Ohm)
5Motor overload protection (MPCB / electronic thermal relay / VFD I^2t parameter) set <= 1.00 x I_FLC (for IEC Service Factor 1.0 motors)
6PTC thermistor / PT100 stator & bearing RTD protection wired to trip VFD/contactor on overtemperature
7For VFD-fed motors: symmetrical 360-degree EMC shielded motor cable terminated with EMC glands at both VFD and motor ends [IEC 60034-25]
8For VFD cable lengths > 50-100 m: dV/dt filter or sine-wave filter installed to limit reflected-wave voltage spikes (< 1300 Vpk on 400 V motors)
9Insulated NDE ceramic/coated bearing and/or carbon-microfiber shaft grounding brush installed on VFD motors >= 75-90 kW
10VFD DC-link capacitors, heatsink cooling fans, and cabinet air filters inspected and free of conductive dust/oil mist
11Mechanical shaft alignment, coupling elastomer condition, and overall vibration velocity (ISO 20816-3 <= 2.8-4.5 mm/s RMS) verified
12Local lockable emergency isolator / maintenance safety switch within sight of the driven machine verified functional