#03Lux / Lighting Verification Report

Project Framework (report reference): IEC 60364-4-41Applicable Standard: EN 12464-1:2021 / EN 15193

Multi-Asset / Multi-Point Equipment Schedule

Inspect multiple transformers, panels, rooms, motors, or RCDs in this module without overwriting previous assets. Each item receives a permanent QR Sticker UID preserved across annual audits.

Sticker UID: OC-LIGH-AECA

Standard Limits, Equations & Space Presets

EN 12464-1:2021 Indoor Workplace Lighting schedules: required maintained illuminance Em, minimum uniformity Uo, Unified Glare Rating limit R_UGL, Colour Rendering Ra, and Room Index K measurement grid sizing.

One-Click Normative Presets (Auto-fills Target Limits)
Governing Equations & Physical Constants
Uo

Uo = Emin / Eavg

Illuminance uniformity on the task area; must meet the space class limit (0.40, 0.60, or 0.70) and cannot exceed 1.00.

K (Room Index)

K = (L x W) / (Hm x (L + W))

Determines minimum number of lux grid measurement points N_min (4, 9, 16, or 25 points) per EN 12464-1 §4.4.1.

LPD

LPD = P_total / (L x W) [W/m2]

Installed Lighting Power Density and normalized efficiency W/m2 per 100 lx (EN 15193-1).

EN 12464-1:2021 Normative Indoor Workplace Illuminance Schedule

EN 12464-1:2021 Section 5 & ANSI/TIA-942
Ref ClauseZone / Activity / Room TypeMaintained Em (Lux)Min Uniformity UoMax Glare R_UGLMin CRI Ra
5.1.1Corridors and circulation areas100 lx0.402840
5.1.2Stairs, escalators, loading ramps150 lx0.402540
5.25.2Electrical switchrooms, plant & generator rooms200 lx0.402560
5.25.4Control rooms & switchboard control desks500 lx0.601980
5.26.1Filing, copying, reception counter300 lx0.401980
5.26.2Writing, typing, reading, VDT office workstations500 lx0.601980
5.26.3Technical drawing / CAD design stations750 lx0.701680
5.26.4Conference and meeting rooms500 lx0.601980
5.29.1Store rooms, cold stores, bulk warehouse aisles100 - 200 lx0.402560
5.10.2Rough mechanical / electrical assembly (cables, transformers)300 lx0.602580
5.10.4Fine electrical assembly (control panels, switchgear wiring)750 lx0.701680
5.10.5Precision electronic workshops, PCB inspection1000 lx0.701690
TIA-942Data center server hall (1 m above floor in aisle)500 lx0.601980

Minimum Illuminance Measurement Grid Points by Room Index K (EN 12464-1 §4.4.1)

EN 12464-1:2021 §4.4.1
Room Index K = L·W / [Hm·(L+W)]Min Grid LayoutMin Number of Measurement Points
K < 1.02 x 2 symmetrical grid4 points minimum
1.0 <= K < 2.03 x 3 symmetrical grid9 points minimum
2.0 <= K < 3.04 x 4 symmetrical grid16 points minimum
K >= 3.05 x 5 symmetrical grid25 points minimum

Exclude a 0.5 m border strip from walls unless the task area extends to the wall.

Measured Inputs

Calculated / Evaluated Results

Select the EN 12464-1:2021 space category (or click a preset in the Standard Annex drawer above) to automatically set the required maintained illuminance Em, uniformity U0 = Emin / Eavg, glare limit UGR_L, and CRI Ra. Enter room dimensions L, W, Hm to verify the mandatory EN 12464-1 §4.4.1 measurement grid point count from Room Index K.

Pending / Not tested — results stay neutral until valid measured values are entered.

  • Maintained Illuminance Em (Office Zone Target >= 500 lx)

    -

    Not tested - enter the measured value. Acceptance: Eavg >= 500 lx maintained illuminance for the selected EN 12464-1 space [EN 12464-1:2021 Section 5]

    Pending
  • Uniformity U0 = Emin / Eavg (Target >= 0.60)

    -

    Not tested - enter the measured value. Acceptance: 0.60 <= U0 <= 1.00 across the task/activity area [EN 12464-1:2021 §4.3]

    Pending
  • Unified Glare Rating UGR (Target <= 19)

    -

    Not tested - enter the measured value. Acceptance: R_UGL <= 19 for the selected task class [EN 12464-1:2021 §4.5]

    Pending
  • Colour Rendering Index Ra (Target >= 80)

    -

    Not tested - enter the measured value. Acceptance: Ra >= 80 for the selected interior zone [EN 12464-1:2021 §4.6]

    Pending
  • Room Index K & Measurement Grid Point Adequacy (EN 12464-1 §4.4.1)

    -

    Not tested - enter the measured value. Acceptance: K < 1 -> 4 pts; 1 <= K < 2 -> 9 pts; 2 <= K < 3 -> 16 pts; K >= 3 -> 25 pts [EN 12464-1:2021 §4.4.1]

    Pending
  • Lighting Power Density (LPD) & Normalized Efficiency

    -

    EN 15193-1 / ASHRAE 90.1 energy efficiency benchmark (LED office target <= 2.5 W/m2 per 100 lx).

    Pending

Verification Checklist (0 / 11)

Pending
  • 1Measurement grid laid out per Room Index K (excluding 0.5 m wall border strip) [EN 12464-1 §4.4.1]

  • 2Lux meter cosine and V(lambda) spectral response corrected with valid calibration certificate

  • 3Extraneous daylight excluded (night survey or blinds closed) or ambient baseline subtracted

  • 4Luminaires aged >= 100 h and thermally stabilised prior to photometric readings

  • 5Workplane measurement height verified (0.75 m sitting task, 0.85 m standing, 0.0 m floor circulation)

  • 6Immediate surrounding area illuminance verified in accordance with EN 12464-1 Table 1

  • 7Surface reflectances within normal range (ceiling 0.7-0.9, walls 0.5-0.8, floor 0.2-0.4)

  • 8No disability or veiled reflection glare observed on VDT screens / control panels

  • 9Temporal light modulation (flicker PstLM <= 1.0 & stroboscopic SVM <= 0.4) verified on rotating machinery

  • 10Failed, dimmed or colour-shifted LED modules/drivers logged for maintenance replacement

  • 11As-built floor plan annotated with grid coordinates and point-by-point lux values