#08Diesel / Gas Generator Inspection
Multi-Asset / Multi-Point Equipment Schedule
Inspect multiple transformers, panels, rooms, motors, or RCDs in this module without overwriting previous assets. Each item receives a permanent QR Sticker UID preserved across annual audits.
Sticker UID: OC-GENE-C5A3Standard Limits, Equations & Space Presets
NFPA 110 Type 10 Emergency Power Supply System (EPSS) 10 s start-to-load requirement, 30% minimum exercise load, and ISO 8528-5 G1/G2/G3 frequency and voltage transient classes.
Measured Inputs
Calculated / Evaluated Results
Acceptance: a Type 10 EPSS must start and accept load within 10 s (NFPA 110 Table 4.1(b)). Steady-state and transient frequency / voltage bands follow the ISO 8528-5 performance class selected below.
Pending / Not tested — results stay neutral until valid measured values are entered.
- Pending
NFPA 110 Minimum Exercise Load (30% Rated)
-
NFPA 110 §8.4.2 requires monthly on-load exercise at >= 30% of nameplate kW rating to prevent diesel wet-stacking.
- Pending
Start to On-Load Time
- s
Not tested - enter the measured value. Acceptance: Type 10 EPSS: the set must accept the emergency load within 10 s [NFPA 110 Table 4.1(b)]
- Pending
Steady State Frequency Band
- %
Not tested - enter the measured value. Acceptance: Class G2: +/-1.5% steady state [ISO 8528-5 Table 4]
- Pending
Transient Frequency Deviation
- %
Not tested - enter the measured value. Acceptance: Class G2: +/-12% on a full load step [ISO 8528-5 Table 4]
- Pending
Frequency Recovery Time
- s
Not tested - enter the measured value. Acceptance: Class G2: recovery within 5 s [ISO 8528-5 Table 4]
- Pending
Transient Voltage Deviation
- %
Not tested - enter the measured value. Acceptance: Class G2: +/-20% on a full load step [ISO 8528-5 Table 5]
- Pending
Fuel Level
- %
Not tested - enter the measured value. Acceptance: Tank >= 75% and sized for the declared EPSS class run time [NFPA 110 §5.5 practice]
- Pending
Starting Battery Voltage
- V
Not tested - enter the measured value. Acceptance: Resting voltage >= 25.2 V for a 24 V system [SAE J537 field convention]
- Pending
Total Run Hours
- h
Compare against the OEM service interval.
Verification Checklist (0 / 18)
1Generator control selector switch verified in 'AUTO' mode with zero active fault lockouts [NFPA 110 §8.4]
2Jacket water block heater operational and maintaining engine coolant at 32-49 degC for immediate cold start
3Engine lube oil level, viscosity, and pressure sender verified; zero oil weepage at crank seals
4Radiator coolant level, glycol freeze/inhibitor concentration, belt tension, and hoses inspected
5Day-tank and bulk fuel levels verified (>= 8-48h autonomy per Tier rating); water separator drained and fuel polished
6Starting battery string (12V/24V) open-circuit, float voltage, specific gravity/conductance, and cranking voltage drop tested
7Static battery charger float/equalize output and low-DC-voltage alarm relay verified
8Motorised intake and discharge ventilation louvres proven to open fully on engine start command
9Exhaust manifold thermal blankets, flexible bellows, silencer, and rain cap intact and leak-free
10Anti-vibration spring/elastomer mounts, foundation anchor bolts, and flexible fuel/electrical connections sound
11Simulated mains failure cold-start test completed: cranking, firing, and load acceptance within <= 10 s (NFPA 110 Type 10)
12Electronic governor (droop / isochronous) steady-state and step-load frequency response verified per ISO 8528-5 Class G2/G3
13Automatic Voltage Regulator (AVR) steady-state voltage regulation (+/-1%) and reactive load sharing verified
14Monthly on-load exercise run conducted at >= 30% rated nameplate kW (or exhaust temp >= OEM minimum) to prevent wet-stacking
15Alternator winding and bearing RTD temperatures, plus stator insulation resistance, within OEM limits
16Engine safety shutdowns proven (overspeed, low oil pressure, high coolant temp, overcrank)
17Local and remote Emergency Stop buttons, automatic fuel shutoff valve, and room fire damper interlocks tested
18BMS / SCADA telemetry alarms (Not-in-Auto, Low Fuel, Charger Fail, Common Fault) verified end-to-end