#16Emergency Egress & Exit Lighting Test
Multi-Asset / Multi-Point Equipment Schedule
Inspect multiple transformers, panels, rooms, motors, or RCDs in this module without overwriting previous assets. Each item receives a permanent QR Sticker UID preserved across annual audits.
Sticker UID: OC-EMER-BBEBStandard Limits, Equations & Space Presets
EN 1838 / BS 5266-1 / NFPA 101 Emergency Escape Lighting requirements: escape route centre line (>= 1.0 lx), anti-panic open area (>= 0.5 lx), high-risk task area (>= 10% of normal, >= 15 lx), 40:1 diversity, and 180 min duration.
Measured Inputs
Calculated / Evaluated Results
EN 1838 / BS 5266-1 acceptance: escape route centre line >= 1 lx, anti-panic open area >= 0.5 lx, high risk task area >= 10% of the normal level with a 15 lx floor, diversity <= 40:1, and the full rated duration on discharge.
Pending / Not tested — results stay neutral until valid measured values are entered.
- Pending
Escape Route Illuminance
- Lux
Not tested - enter the measured value. Acceptance: >= 1 lx on the centre line of the escape route [EN 1838 §4.2.2]
- Pending
Open (Anti-Panic) Area Illuminance
- Lux
Not tested - enter the measured value. Acceptance: >= 0.5 lx at floor level, excluding a 0.5 m border [EN 1838 §4.2.3]
- Pending
High Risk Task Area Illuminance
-
Not tested - enter the measured value. Acceptance: >= 10% of the normal maintained level and never below 15 lx [EN 1838 §4.2.4]
- Pending
Uniformity Emax : Emin
-
Not tested - enter the measured value. Acceptance: 1:1 <= Emax:Emin <= 40:1 diversity along the escape route [EN 1838 §4.2.2]
- Pending
Duration Test
-
Not tested - enter the measured value. Acceptance: Full rated duration on discharge (1 h non-sleeping risk, 3 h sleeping risk) [EN 1838 §4.5 / BS 5266-1]
- Pending
Response Time to Full Output
- s
Not tested - enter the measured value. Acceptance: 50% of the required level within 5 s and the full level within 60 s [EN 1838 §4.3]
Verification Checklist (0 / 13)
1Emergency escape route centre-line illuminance verified >= 1.0 lux at floor level with uniformity Emax/Emin <= 40:1 [EN 1838 §4.2]
2Open area (anti-panic > 60 m2) horizontal illuminance verified >= 0.5 lux with uniformity Emax/Emin <= 40:1 [EN 1838 §4.3]
3High-risk task area illuminance verified >= 10% of normal maintained lux (and never < 15 lux) with uniformity Emin/Eavg >= 0.10 [EN 1838 §4.4]
450% of required illuminance achieved within 5 s and 100% achieved within 60 s of mains failure
5Points of emphasis illuminated (every exit door, staircase flight, level change, corridor intersection, fire call point, fire extinguisher, first-aid post, and outside final exit)
6Internally illuminated ISO 7010 running-man exit signs visible within D = 200 x h (and D = 100 x h for externally lit signs) [EN 1838 §5]
7Full rated autonomy duration test (180 min / 3 h for sleeping/public/industrial risks; 60 min minimum) completed and passed [BS 5266-1 / EN 50172]
8Green LED battery charge indicator healthy on all self-contained luminaires after mains restoration
9NiCd / NiMH / LiFePO4 battery manufacture/installation date verified within 4-year replacement lifecycle
10Central Battery System (CBS) / Static Inverter sub-circuit monitoring and fire-resistant cabling (EN 50200 PH30/PH120) verified where fitted
11Key-operated test switches or DALI automated emergency self-test controller (IEC 62034) verified per lighting sub-circuit
12Recharge recovery period verified (capable of meeting full rated duration again within 24 hours of recharge)
13Emergency lighting logbook updated with monthly functional and annual full-duration test certificates [EN 50172 §7.2]