#16Emergency Egress & Exit Lighting Test

Project Framework (report reference): IEC 60364-4-41Applicable Standard: BS 5266 / NFPA 101

Multi-Asset / Multi-Point Equipment Schedule

Inspect multiple transformers, panels, rooms, motors, or RCDs in this module without overwriting previous assets. Each item receives a permanent QR Sticker UID preserved across annual audits.

Sticker UID: OC-EMER-BBEB

Standard Limits, Equations & Space Presets

EN 1838 / BS 5266-1 / NFPA 101 Emergency Escape Lighting requirements: escape route centre line (>= 1.0 lx), anti-panic open area (>= 0.5 lx), high-risk task area (>= 10% of normal, >= 15 lx), 40:1 diversity, and 180 min duration.

One-Click Normative Presets (Auto-fills Target Limits)

Measured Inputs

Calculated / Evaluated Results

EN 1838 / BS 5266-1 acceptance: escape route centre line >= 1 lx, anti-panic open area >= 0.5 lx, high risk task area >= 10% of the normal level with a 15 lx floor, diversity <= 40:1, and the full rated duration on discharge.

Pending / Not tested — results stay neutral until valid measured values are entered.

  • Escape Route Illuminance

    - Lux

    Not tested - enter the measured value. Acceptance: >= 1 lx on the centre line of the escape route [EN 1838 §4.2.2]

    Pending
  • Open (Anti-Panic) Area Illuminance

    - Lux

    Not tested - enter the measured value. Acceptance: >= 0.5 lx at floor level, excluding a 0.5 m border [EN 1838 §4.2.3]

    Pending
  • High Risk Task Area Illuminance

    -

    Not tested - enter the measured value. Acceptance: >= 10% of the normal maintained level and never below 15 lx [EN 1838 §4.2.4]

    Pending
  • Uniformity Emax : Emin

    -

    Not tested - enter the measured value. Acceptance: 1:1 <= Emax:Emin <= 40:1 diversity along the escape route [EN 1838 §4.2.2]

    Pending
  • Duration Test

    -

    Not tested - enter the measured value. Acceptance: Full rated duration on discharge (1 h non-sleeping risk, 3 h sleeping risk) [EN 1838 §4.5 / BS 5266-1]

    Pending
  • Response Time to Full Output

    - s

    Not tested - enter the measured value. Acceptance: 50% of the required level within 5 s and the full level within 60 s [EN 1838 §4.3]

    Pending

Verification Checklist (0 / 13)

Pending
  • 1Emergency escape route centre-line illuminance verified >= 1.0 lux at floor level with uniformity Emax/Emin <= 40:1 [EN 1838 §4.2]

  • 2Open area (anti-panic > 60 m2) horizontal illuminance verified >= 0.5 lux with uniformity Emax/Emin <= 40:1 [EN 1838 §4.3]

  • 3High-risk task area illuminance verified >= 10% of normal maintained lux (and never < 15 lux) with uniformity Emin/Eavg >= 0.10 [EN 1838 §4.4]

  • 450% of required illuminance achieved within 5 s and 100% achieved within 60 s of mains failure

  • 5Points of emphasis illuminated (every exit door, staircase flight, level change, corridor intersection, fire call point, fire extinguisher, first-aid post, and outside final exit)

  • 6Internally illuminated ISO 7010 running-man exit signs visible within D = 200 x h (and D = 100 x h for externally lit signs) [EN 1838 §5]

  • 7Full rated autonomy duration test (180 min / 3 h for sleeping/public/industrial risks; 60 min minimum) completed and passed [BS 5266-1 / EN 50172]

  • 8Green LED battery charge indicator healthy on all self-contained luminaires after mains restoration

  • 9NiCd / NiMH / LiFePO4 battery manufacture/installation date verified within 4-year replacement lifecycle

  • 10Central Battery System (CBS) / Static Inverter sub-circuit monitoring and fire-resistant cabling (EN 50200 PH30/PH120) verified where fitted

  • 11Key-operated test switches or DALI automated emergency self-test controller (IEC 62034) verified per lighting sub-circuit

  • 12Recharge recovery period verified (capable of meeting full rated duration again within 24 hours of recharge)

  • 13Emergency lighting logbook updated with monthly functional and annual full-duration test certificates [EN 50172 §7.2]